SER-10 RS-485 without fail-safe biasing

Severity Status Implementation
warning planned mid, depends on NET-7

Looks at. Transceiver failsafe capability (part data), bias resistors.

What it catches. An RS-485 bus with a transceiver that has no built-in idle-bus failsafe and no external bias network (A pulled up, B pulled down through resistors of a few hundred ohms).

Why it matters. When no driver is active, the terminated bus sits at 0 V differential: inside the ±200 mV undefined window of a classic receiver. The receiver output then follows noise, and the UART sees start bits and framing errors between every message. Modern transceivers shift their threshold to fail safe (output high on an idle, open or shorted bus), but their noise margin is small, and older parts (SN75176B, MAX485 class) have none.

Example. An SN75176B on a 5 V bus with 120 Ω at both ends: its datasheet's own design procedure adds external failsafe biasing for +200 mV. SLLA272 works the numbers: with 4.75 V minimum supply, 250 mV target and 120 Ω line, two 523 Ω bias resistors at one end.

How to check. For each RS-485 transceiver, read from part data whether it has idle-bus failsafe (NET-7); if not, look for a resistor from A to a rail and from B to ground on the bus.

Fix. Use a transceiver with built-in failsafe (THVD1450, SN65HVD72 class), or add the bias pair at one node only; its value per SLLA272 equation 2 or SLYT324.

References. SLLA272 §7 (Failsafe, equation 2, Figure 7-1); SLLA070 §3 (Failsafe Operation); SLYT324; SN75176B §7.2.2; THVD1450 §10.2.1.4 (Receiver Failsafe).