SER-24 RS-485 unit-load budget exceeded¶
| Severity | Status | Implementation |
|---|---|---|
| warning | planned | mid, depends on NET-7, CFG-2 |
Looks at. Transceiver unit load (part data), bias network, node count (project).
What it catches. An RS-485 bus whose nodes and bias network together load the driver beyond 32 unit loads.
Why it matters. TIA-485-A sizes its drivers to deliver at least 1.5 V differential into 54 Ω: two 120 Ω terminations in parallel with 32 unit loads (one UL is about 12 kΩ). Every node adds its receiver's load (1, ½, ¼ or ⅛ UL), and failsafe bias resistors add up to 20 UL. Past the budget the differential voltage at the far end drops below the receivers' threshold plus noise.
Example. 64 nodes with ⅛ UL transceivers (THVD1450) look comfortable at 8 UL, but the 523 Ω bias pair of SER-10 costs up to 20 UL: SLLA272 gets N = (32 − 20) / UL, so 96 devices at ⅛ UL instead of 256. Mixing in old full-UL nodes (SN75176B) eats the rest.
How to check. Sum unit loads from part data per transceiver (NET-7) times the node count from the project (CFG-2), plus the load of bias networks found on the board (SER-10).
Fix. Fewer UL per node (⅛-UL transceivers), weaker or single bias networks, or a repeater to split the bus.
References. SLLA272 §8 (Bus Loading, equation 3); SLLA070 §2.2.3 (1.5 V minimum VOD into 2 × 27 Ω); THVD1450 §10.2.1.3 (Bus Loading); TIA-485-A.