SER-13 CAN termination wrong for the node's place¶
| Severity | Status | Implementation |
|---|---|---|
| warning | planned | mid, depends on NET-7, CFG-2 |
Looks at. CAN lines, termination, the node's place on the bus.
What it catches. A CAN node with no termination although it sits at a bus end, or with a fixed 120 Ω although it sits in the middle of the bus.
Why it matters. ISO 11898-2 wants exactly two 120 Ω terminations, one at each end of the line: about 60 Ω seen by every driver. A missing one leaves reflections; an extra one in the middle drops the load to 40 Ω, the differential dominant voltage drops and margins shrink, and with three or four "helpfully terminated" nodes the bus stops working. TI's TCAN1042 note: place terminations so two always exist, even when nodes are removed.
Example. B125 needs a bigger termination resistor in rev B: the split pair is 2 × 60.4 Ω in 0603. A dominant bit puts only ~1 V on each half, but a wiring fault (CAN_H on a 24 V supply wire) drives the transceiver's short circuit current through them, and TI asks to size the termination's power rating for exactly that case.
How to check. Count the termination resistors on the node's CAN lines (fixed, or switchable through a relay or jumper, NET-10) and compare with the project's statement of where the node sits (CFG-2). Without it: suggest a switchable termination.
Fix. Switchable termination (relay, jumper, DIP switch) on nodes that can be anywhere; fixed termination only on nodes that are always at an end. Rate the resistors for the bus fault current.
References. TCAN1042H §10.2.2.1 (CAN Termination), §9.3.6 (short-circuit current and termination power rating); SLOA101 §5; B125 rev B change list; ISO 11898-2:2016.