SER-9 RS-485 bus without termination at both ends

Severity Status Implementation
error planned mid, depends on NET-7, CFG-2

Looks at. RS-485 A/B nets, termination resistor, the node's place on the bus.

What it catches. An RS-485 node that the project marks as a bus end (or the only node, as on a point-to-point link) with no 120 Ω (or 100-130 Ω) resistor between A and B, fitted or selectable.

Why it matters. RS-485 runs on twisted pair of about 120 Ω; an unterminated end reflects each edge back. At 9600 baud over a few metres it hardly matters, but at hundreds of kbit/s or over 100 m the reflections cross the ±200 mV threshold and corrupt bits. Termination also sets the idle differential voltage together with failsafe biasing (SER-10).

Example. A Modbus RTU sensor board with a THVD1450 at 115 200 baud on 300 m of cable, the last device on the line, with no termination footprint: the installer adds a resistor in the terminal block, or the link runs with errors on hot days.

How to check. Find RS-485 transceivers (pins A/B or Y/Z, NET-7); look for a 100-130 Ω resistor across A-B (directly, through a jumper or a switch). Whether the node is a bus end is a project setting (CFG-2); without it, report "no termination option" as a suggestion.

Fix. A 120 Ω across A-B at the node, switchable (jumper, DIP switch) if the board can sit anywhere on the bus. Size the resistor for a driver short (RS-485 drivers deliver up to ~250 mA into a short).

References. SLLA272 §6 (Bus Termination and Stub Length, Figure 6-1); SLLA070 §4 (termination techniques), §2.2.5 (250 mA short-circuit limit); TIA-485-A; Wikipedia, RS-485.