PIN-15 Fuse voltage rating below the supply voltage

Severity Status Implementation
warning planned mid, depends on NET-5, CFG-2

Looks at. Fuse voltage rating (and AC or DC) from the MPN, the rail voltage.

What it catches. A fuse whose voltage rating (for DC, the DC rating) is below the voltage of the rail it is on.

Why it matters. The voltage rating is the voltage at which the fuse is guaranteed to clear the fault: when the element melts, the arc across the gap must go out. At a higher voltage, and in DC where there is no zero crossing, the arc can keep burning, the fuse body ruptures and the circuit is not interrupted. The fuse "works" in every test until the fault it is there for.

Example. A 32 V DC automotive blade fuse on a 48 V telecom input: it carries the load fine and fails to break a short.

How to check. Voltage rating and AC/DC from the MPN; the rail voltage from the net name or the project (NET-5, CFG-2), with its maximum, not its nominal.

Fix. A fuse rated at or above the maximum supply voltage, with a DC rating for DC rails.

References. Fuseology "Selection Factors" 2 (application voltage: the fuse rating must be equal to or greater than the available circuit voltage) and "Voltage Rating"; Wikipedia, Fuse (electrical).